NDB2LE-63 series residual current unit clipped onto the right side of NDB2-63 series MCBs to protection against earth leakage faults ,which is used in low voltage electrical distribution system in industry, real estate, power, telecom and construction field.
2.Model:
3.Main technical parameters
Electrical parameters
○ Rated working voltage (Ue):AC230/240V(1P+N、2P) AC380/400/415V(3P、3P+N、4P)
Rated residual making and breaking capacity(IΔm):600A
Mechanical & electrical life: 10000 times
Isolation function:
Overcurrent visualization
Wiring
Adopt tunnel type wiring
Connection capability: 1mm2 to 35 mm2
Meet a criterion
○ GB 16917.1、IEC 61009-1、GB16917.22、IEC61009-2-2
4.Working conditions
Altitude: ≤2000m
Ambient temperature: -25℃~+55℃
Storage temperature: -30℃~+70℃
Relative air humidity ≤95%
Pollution degree: 2
5.Tripping curves (ambient temperature 30℃)
B curve
Non-inductive or micro-inductive loads
Rated current:1~63A
Tripping characteristic: instantaneous trip between 3In to 5In.
B Curve
C curve
Illumination distribution system
Rated current:1~63A
Tripping characteristic: instantaneous trip between 5In to 10In
C Curve
D curve
Industrial distribution system
Rated current:1~63A
Tripping characteristic: instantaneous trip between 10In to 14In
D Curve
6.Outline dimensions and installation
1P+N
2P
3P
3P+N
4P
7.Mounting
Modularized structure, can be easily installed in TH35mm×7.5 Standard DIN rail.
8.Packaging and storage
8.1Maximum packing quantity
1N-pole: 4 pieces in a box, 12 boxes in an overwrap carton. 2-pole: 3 pieces in a box, 12 boxes in an overwrap carton. 3-pole: 2 pieces in a box, 12 boxes in an overwrap carton. 3N-pole: 1 pieces in a box, 12 boxes in an overwrap carton. 4-pole: 1 pieces in a box, 12 boxes in an overwrap carton.
8.2 The products should be stored in the warehouse where there is ventilation. The relative humidity there should not exceed 80%, and the ambient temperature there is between
-30℃ to +70℃. In addition, there should not be acidic, alkaline and corrosive gas in the air.
The products should not be deposited more than 3 years in the above mentioned conditions since the producing date.
9.Accessories
OF2 auxiliary contact: Installed on the left hand of the NDB2LE-63 series RCBOs to indicate tripping status of the breaker.
SD2 alarm contact: Installed on the left hand of the NDB2LE-63 series RCBOs to indicate failure tripping status of the breaker.
●MX+OF2 shunt trip release :Installed on the left hand of NDB2LE- 63 series RCBOs, remote control of the circuit breaker’s tripping;
10.Notices
Take no responsibility for problems occurred by disassembly privately.
RCBO can’t provide protection in the cases that touch two phase line synchronously.
Please don’t perform insulating resistance test or voltage-withstand test on the product directly or indirectly by megohmmeter or similar test devices. If you need, we can offer validated certificate about the term.
When test insulating resistance of the engineering circuit, the outlet terminal (at least one line) must be disconnected to avoid the misunderstanding of the products’ quality or damage of the products.
The power line should be connected to ‘LINE’, while another terminal to ‘LOAD’. Don’t connect contrarily. Otherwise the product will be damaged when the test button is pressed or there is earth leakage in the circuit.
Please make sure reliable connection to avoid fault tripping or damage of terminals caused by exceptional heat resulting from unsuitable connection.
Simulating test should be made once a month by pressing the test button to check whether the circuit breaker works normally. If RCBO is abnormal, it should be replaced.
1、Applicable scope and purpose ●Short -circuit protection ●Over-load protection ●Control ●Isolation ●DC system protection NDB2Z-63 dedicated to the low voltage power distribution system of industrial, buildings, energy communi...
1、Application The NDB2LM-40 series of residual current action circuit breakers (RCBO) are applicable to the domestic and similar places and some places with a high sensitivity, which are also applicable to laboratories, service industries and sma...
1.Applicable Scope and Purpose of Circuit BreakerThe NDM2L-630 molded case circuit breaker with the residual current protection (hereinafter referred to as circuit breaker) applies to infrequent switching of circuits with the AC 50/60Hz, the worki...
1.Application Scope and Purpose ●Short-circuit protection●Overload protection●Current leakage●Isolation leakageThe NDB1LE-100 series of residual current action circuit breakers provide the ground leakage, direct or indirect electric shock by human...
Enviar una consulta sobre un producto
Nos pondremos en contacto con usted en un plazo de 24 horas.